Specifications
Raychem 3 pieces joint up to 145 KV
| Technical data: | 145 kV |
|
||
| Rated voltage Uo/U(Um) | kV | 76/132 (145) | ||
| Basic impulse level | kV | 650 | ||
| Max. continuous operating temperature | °C | 90 | ||
| Max. conductor emergency temperature | °C | 150 | ||
| Conductor short circuit temperature | °C | 250 | ||
| Short circuit current (sheath) | kA/1sec | 40 | ||
| For shield break joints: | ||||
| DC voltage between metallic | ||||
| sheath/screen | kV | 20 | ||
| DC voltage between metallic | ||||
| sheath/screen and earthed exterior | kV | 20 | ||
| Lighning impulse voltage between metallic | ||||
| sheath/screen | kV | 75 | ||
| Lightning impulse voltage between metallic | ||||
| sheath/scren and earthed exterior | kV | 37.5 | ||
| Application Range: | ||||
| Conductor | mm² | 1200 | ||
| Diameter over insulation | mm. | 43 – 84 | ||
| Catalogues No. | Baht/ 1 core kit |
| EHVS – 145 | 300000 ฿ |
| 1. Mechanical connector |
Straight joint |
| 2. Silicone rubber adapter body | |
| 3. Silicone rubber main body | |
| 4. Inner electrode/Faraday cage | |
| 5. Deflector | |
| 6. Outer screen | |
| 7. Copper mesh |
Ground separated joint |
| 8. Solderless shield connection | |
| 9. Sealant / Mastic | |
| 10. Insulating tubes | |
| 11. Outer protection with integrated moisture barrier |