SKU: G02
Category: Surge arrester and Surge counter
Bowthorpe polymer arrester 96KV line discharge class 3
Descriptions
Specifications
Bowthorpe EMP Transmission Surge Arrester
PCA Range
BOW PCA 3E96L2E1M8 | 200,000 Baht/set |
96kV Polymer arrestor line discharge class 3
Residual voltage 230kV Energy capability with 7.8kJ/kV at Ur (Thermal) |
Nominal discharge current 10kA
Metal Oxide polymer arrester for outdoor application IEC 60099-4 ; (2014) |
Surge Arrester Characteristics | |||||||
Rated voltage | Ur: | 96 | kV | ||||
Continuous operating voltage | Uc: | 76.8 | kV | ||||
TOV Capability (With prior energy) | Tr: | 110 | kV for 1s | ||||
105 | kV for 10s | ||||||
Rated short circuit current | 65 | kA |
Cantilever Load | |||||||||
Safe long‐term load (SLL) | 2 | kNm | |||||||
Safe short‐term load (SSL) | 2.5 | kNm | |||||||
Dry impulse voltage ‐ 1.2/50 µs | 672 | kV | |||||||
Wet power frequency voltage | 358 | kV | |||||||
Flashover Distance | 1059 | mm | |||||||
Creepage Length | 4500 | mm | |||||||
Minimum distance between Phase Centers | 720 | mm | |||||||
Minimum distance between Phase to Earth | 630 | mm | |||||||
Height | 1085 | mm | |||||||
Approx. Weight | 27.5 | kg |
Line Termination | Earth Termination | Mounting | ||||||||||||
L1 | E1 | M5 | ||||||||||||
M16 stud assembly | 2 x M10x20mm | 4 Hole Pedestal Base | ||||||||||||
Hexagonal headed set screws and spring washers | 280 PCD or 3 x 15mm slots on 200mm – 254mm PCD | |||||||||||||
L2 | E2 | M4 | ||||||||||||
Line Clamp to suit cables up to Ø16 mm | Earth Clamp to suit cables up to Ø16 mm | Set of 4 Ø 89 x 76 | ||||||||||||
Polyfibre Base Insulators | ||||||||||||||
Supplied with M5 Pedestal Base | ||||||||||||||
L5 | E5 | M8 | ||||||||||||
Line Clamp to suit cables from Ø16 mm to Ø 35 mm | Earth Clamp to suit cables from Ø16 mm to Ø 35mm | Set of 3 Ø 89 x 76 | ||||||||||||
Polyfibre Base Insulators | ||||||||||||||
Supplied with M5 Pedestal Base | ||||||||||||||
L6 | ||||||||||||||
Aluminium Stem | ||||||||||||||
Ø30 x 80mm high | ||||||||||||||
L21 | ||||||||||||||
4 Hole NENA Pad | ||||||||||||||
Maximum Residual Voltages | ||||||||||||||
Lightning current impulse | Steep lightning | Switching current | ||||||||||||
8/20 µs | current impulse 1/20 µs | impulse 30/60 µs | ||||||||||||
5 kA | 10 kA | 20 kA | 40 kA | 10 kA | 20 kA | 125 A | 250 A | 500 A | 1000 A | 2000 A | 3000A | |||
219 kV | 230 kV | 249 kV | 276 kV | 242 kV | 260 kV | 180 kV | 184 kV | 189 kV | 196 kV | 203 kV | 210 kV |
Power frequency voltage versus time | |
Marking PCA3E‐96 Ur: 96.0 kV Uc: 76.8 kV IEC 60099‐4 Designation SM ISC 65 kA Serial No Energy 7.8 kJ/kV‐Ur Nom Disc Curr 10 kA Qrs: 2.2 C Manufacturing Year |